GIL ( Gas Insulated Transmission Line )

Back
GIL
GIS Bus
High-Voltage-Testing
Tunnel-Installations
Substation-Line
Horizontal-Tunnel
 

Compact Gas Insulated Transmission

mm Enclosure Diameter Conductor Diameter Phase Spacing
145kV 241 89 381
242kV 307 102 457
362kV 375 127 559
550kV 508 178 711
800kV 622 178 813
  • Right of Way Requirement
  • 145kV CGIT Line: 1.2 meters wide
  • 242kV CGIT Line: 1.5 meters wide
  • 362kV CGIT Line: 1.8 meters wide
  • 550kV CGIT Line: 2.1 meters wide

Design Features

  • Section lengths up to 18 meters
  • Bolted enclosure field joints with double o-ring seal Field welded joint design available
  • Tripost conductor support insulators with particle traps
  • Corrosion resistant aluminum enclosure
  • Factory assembled and fully tested shipping assemblies
  • Experience with vertical and underground systems