Gas Insulated Switchgear (GIS) 245Kv

Back

Complete three-phase encapsulated design with single break per phase

  • Harmonic and consistent operating mechanism portfolio for circuit breaker as well as for disconnector and earthing switch
  • Lightweight enclosures of aluminum with good conductivity, no eddy-current losses and a high resistance to corrosion
  • Proven metal-to-metal flange connections, ensuring high gas tightness and return-current conductivity
  • Increased personnel safety and electromagnetic compatibility
  • Short erection times and high reliability, by providing large transport units assembled and tested in the factory
  • The ways of installation is very flexible either horizontal or vertical
 
Rated voltage 252kV
Rated current 2000A 2500A 3150A 4000A
Rated frequency 50 Hz
Rated short-time withstand current(3s) 50kA
Rated peak withstand current 125 kA
Rated short-circuit breaking current 50kA
Rated making current 125kA
Rated power frequency withstand voltage(1 min.) 460kV
Rated lightning impulse withstand voltage 1050kV
Leakage rate/ year and gas compartment 0.5%
Operating sequence O-0.3s-CO-180s-CO
Ambient temperature -25…+40 ℃