Boom Current Monitors

Back

Rugged, Dependable Design
Automatic Safety Check for shorted or mis-wired cables

The BCM-44 and BCM-44B are state of the art current monitors designed for continuous operation during bare-hand work. The BCM has an adjustable set point (5 presets also available on BCM-44B) between 1 and 400 microamperes AC or DC. A 90-dB horn sounds an audible warning if this current set point is ever exceeded during use.

The BCM-44 and BCM-44B are extremely rugged and dependable current monitors. Designed for operation a variety of weather conditions, the BCM provides the security needed for bare-hand live-line work.

VON BCM Specifications

 

BCM 44

BCM 44-B

Display Type

128 by 64 pixel wide temperature range LCD display. A microprocessor-controlled heater allows operation in extreme low temperatures.

Ranges

Two Ranges:
Low Range: 0-99 microamps A.C. or D.C. with .1 µA resolution. 
High Range: 0-500 microamps A.C. or D.C. with 1 µA resolution.

Voltage Drop

Less than 1 volt full scale

Measurement
System

True RMS AC or DC within 1% of full scale

Preset Alarm Setpoint(s)

Up to 6. Preset values are normally factory set to 27, 40, 66, 93, 133, and 289 microamps. Other preset values are available by request. The presets can be changed in the field as desired.

Adjustable Alarm Setpoint(s)

Adjustable threshold can be set from 1 μA to full scale by a front panel mounted 10-turn control.

Set point
Accuracy

Absolute

Shorted metering
circuit monitor

Continuous

Metering circuit
continuity monitor

Continuous

Audible Alarm

Internal 106DB multi-tone horn sounds when current exceeds setpoint, or when measuring lead is accidentally grounded.

External Alerting Device

A contact is provided to activate an external audible or visible alerting device. The output from this contact can provide either ground or switched input voltage.

Power
Requirements

12 or 24 volts D.C. negative ground. The monitor draws .04 amps steady state and .75 amps with the horn sounding. The display heater can draw up to .75 amps additional in extremely cold weather. 24 volt D.C. negative ground current draw is about half of the 12 volt current draw values.

Enclosure

Precision die-cast aluminum case
4.72” (12cm) x 8.66” (22cm) x 3.14”
(8cm) with external mounting brackets

Weight

5 Lbs. (2.3kg)

Environmental

-20˚ to +140˚F (-30˚ to +60˚C) Sealed to IP67 equivalent

Input for test

UHF coaxial connector

7 pin Amphenol receptacle
 

Input for
Power

3 pin Amphenol receptacle
 

3 pin Amphenol receptacle
 

Test Cable

25’ (7.6m) shielded coaxial cable
provided

4’ (1.2m) shielded six conductor cable
provided

Power Cable

4’ (1.2m) three conductor cable provided